User Guide InfraStruxure 150kVA Power Distribution Unit 58
orSubxxxx
Access: Administrator, Device
Description: This category of alarm mapping commands associates a subfeed threshold alarm with the
output relay/relays designated in the parameters. With no parameter, display the current associated
relays.
Subfeed alarm association commands:
orSub1MxI
orSub1HiI
orSub1LoI
orSub1MnI
orSub1Brk
orSub2MxI
orSub2HiI
orSub2LoI
orSub2MnI
orSub2Brkr
Parameters: [<relay> <enable|disable>]
relay = output relay to be triggered(normally 1|2|3|4).
Example:
apc> orSub1Brkr
1. Subfeed 1Breaker Position,1,disable,2,disable,3,disable,4,disable
apc> orSub1Brkr 3 enable
1. Subfeed 1 Breaker Position,1,disable,2,disable,3,enable,4,disable
apc> orpdBrkrPosition
1. Subfeed 1 Breaker Position,1,disable,2,disable,3,enable,4,disable
orSysxxxxx
Access: Administrator, Device
Description: This category of alarm mapping commands associates a system output threshold alarm
with the output relay/relays designated in the parameters. With no parameter, display the current
associated relays.
System output alarm association commands:
orSysFreq
orSysMxI
orSysHiI
orSysLoI
orSysMnI
orSysMxV
orSysHiV
orSysLoV
orSysMnV