APC AP8868 Podręcznik Użytkownika

Przeglądaj online lub pobierz Podręcznik Użytkownika dla Jednostki dystrybucji zasilania (PDU) APC AP8868. APC AP8868 power distribution unit PDU Instrukcja obsługi

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj

Podsumowanie treści

Strona 1 - User Guide

User GuideMetered Rack Power Distribution UnitAP88XX

Strona 2 - Contents

2Metered Rack PDU User GuideAccess Priorities for Logging onOnly one user at a time can log on to the Rack PDU. The priority for access, beginning wit

Strona 3

92Metered Rack PDU User GuideTroubleshootingRack PDU Access ProblemsFor problems that persist or are not described here, see the back cover of this ma

Strona 4

Metered Rack PDU User Guide93Appendix A: List of Supported CommandsNetwork Management Card Command Descriptions?aboutalarmcount [-p [all | warning | c

Strona 5

94Metered Rack PDU User Guideradius [-a <local | radiusLocal | radius> (Access)][-p1 <primary server>][-s1 <primary server secret>][

Strona 6

Metered Rack PDU User Guide95Device Command DescriptionsbkLowLoad[[id#:]<“all” | bank#> <current>]bkNearOver[[id#:]<“all” | bank#> &

Strona 7

10/2012990-3429D-001APC Worldwide Customer SupportCustomer support for this or any other APC product is available at no charge in any of the following

Strona 8

Metered Rack PDU User Guide3Watchdog FeaturesOverviewTo detect internal problems and recover from unanticipated inputs, the Rack PDU uses internal, sy

Strona 9 - Introduction

4Metered Rack PDU User GuideSpecific assignment of Display IDs. Follow the instructions below before powering up any of the Rack PDUs in the group. If

Strona 10 - Types of User Accounts

Metered Rack PDU User Guide5Establish Network SettingsNote: Disregard the procedures described in this section if you have StruxureWare Data Center Ex

Strona 11 - Network Port Sharing

6Metered Rack PDU User GuideWhen the Rack PDU reboots, the BOOTP server provides it with the TCP/IP settings.• If you specified a bootup file name, t

Strona 12 - Getting Started

Metered Rack PDU User Guide7Command Line Interface1. Log on to the command line interface. See “Log on to the Command Line Interface” on page 14.2. Co

Strona 13 - Establish Network Settings

8Metered Rack PDU User GuideRecovering from a Lost PasswordYou can use a local computer (a computer that connects to the Rack PDU or other device thro

Strona 14 - 04) is the length

Metered Rack PDU User Guide9Rack PDU Front PanelNote: Your APC product is configured so the display backlight turns off after 10 minutes of inactivity

Strona 15 - Command Line Interface

10Metered Rack PDU User GuideItem FunctionOK, Warning, Overload LED Indicates the status of the Rack PDU load. See “Load indicator LED” on page 13.T

Strona 16 - 8Metered Rack PDU User Guide

Metered Rack PDU User Guide11Display Tree Example 1

Strona 17 - Rack PDU Front Panel

ContentsMetered Rack PDU User Guide iIntroduction ... 1Product Features. . . . . . .

Strona 18 - Item Function

12Metered Rack PDU User GuideDisplay Tree Example 2

Strona 19 - Display Tree Example 1

Metered Rack PDU User Guide13Network Status LED10/100 LEDLoad indicator LEDThe load indicator LED identifies overload and warning conditions for the R

Strona 20 - Display Tree Example 2

14Metered Rack PDU User GuideCommand Line InterfaceAbout the Command Line InterfaceYou can use the command line interface to view the status of and co

Strona 21 - Load indicator LED

Metered Rack PDU User Guide15Local access to the command line interfaceFor local access, use a computer that connects to the Rack PDU through the seri

Strona 22

16Metered Rack PDU User Guide• A Stat field reports the Rack PDU status.Stat : P+ N4 N6Note: If P+ is not displayed, contact APC support staff.Using t

Strona 23 - About the Main Screen

Metered Rack PDU User Guide17Command SyntaxExample of a command that supports multiple options: user [-an <admin name>] [-ap <admin password&

Strona 24

18Metered Rack PDU User GuideCommand Response CodesThe command response codes enable scripted operations to detect error conditions reliably without h

Strona 25 - Command Syntax

Metered Rack PDU User Guide19Network Management Card Command DescriptionsAccess: Administrator, Device UserDescription: View a list of all the CLI com

Strona 26 - Command Response Codes

20Metered Rack PDU User GuidebootAccess: Administrator onlyDescription: Define how the Rack PDU will obtain its network settings, including the IP add

Strona 27 - Metered Rack PDU User Guide19

Metered Rack PDU User Guide21consoleAccess: Administrator onlyDescription: Define whether users can access the command line interface using Telnet, wh

Strona 28 - 20Metered Rack PDU User Guide

Metered Rack PDU User Guide iiLog on to the Command Line Interface . . . . . . . . . . . . . . . . . . . . . .14Remote access to the command line int

Strona 29 - Access: Administrator only

22Metered Rack PDU User GuidedateAccess: Administrator onlyDefinition: Configure the date used by the Rack PDU.To configure an NTP server to define t

Strona 30 - 22Metered Rack PDU User Guide

Metered Rack PDU User Guide23dnsAccess: Administrator onlyDefinition: Configure the manual Domain Name System (DNS) settings.eventlogAccess: Administ

Strona 31 - Metered Rack PDU User Guide23

24Metered Rack PDU User GuideFTPAccess: Administrator onlyDescription: Enable or disable access to the FTP server. Optionally, change the port setting

Strona 32 - 24Metered Rack PDU User Guide

Metered Rack PDU User Guide25pingAccess: Administrator, Device UserDescription. Determine whether the device with the IP address or DNS name you spec

Strona 33 - Metered Rack PDU User Guide25

26Metered Rack PDU User GuideradiusAccess: Administrator onlyDescription: View the existing RADIUS settings, enable or disable RADIUS authentication,

Strona 34 - 26Metered Rack PDU User Guide

Metered Rack PDU User Guide27resetToDefAccess: Administrator onlyDescription: Reset all parameters to their default.Example: To reset all of the confi

Strona 35 - Metered Rack PDU User Guide27

28Metered Rack PDU User GuidetcpipAccess: Administrator onlyDescription: View and manually configure these network settings for the Rack PDU: Example

Strona 36 - 28Metered Rack PDU User Guide

Metered Rack PDU User Guide29userAccess: Administrator onlyDescription: Configure the user name, password, and inactivity timeout for the Administrato

Strona 37 - Metered Rack PDU User Guide29

30Metered Rack PDU User GuidexferINIAccess: Administrator onlyDescription: Use XMODEM to upload an INI file while you are accessing the command line i

Strona 38 - Access: Administrator only

Metered Rack PDU User Guide31Device Command DescriptionsNetwork Port Sharing CommandsThe Command Line Interface allows commands to be sent to guest Ra

Strona 39

Metered Rack PDU User Guide iiiDevice Command Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31Network Port Sharing Commands .

Strona 40 - 32Metered Rack PDU User Guide

32Metered Rack PDU User GuidebkOverLoadAccess: Administrator, Device UserDescription: Set or view the bank overload threshold current in amps. You can

Strona 41 - Metered Rack PDU User Guide33

Metered Rack PDU User Guide33devNearOverAccess: Administrator, Device UserDescription: Set or view the near-overload threshold in kilowatts for the de

Strona 42 - 34Metered Rack PDU User Guide

34Metered Rack PDU User GuidehumLowAccess: Administrator, Device UserDescription: Set or view the low humidity threshold as a percent of the relative

Strona 43 - Metered Rack PDU User Guide35

Metered Rack PDU User Guide35phLowLoadAccess: Administrator, Device UserDescription: Set or view the phase low-load threshold in kilowatts. To specify

Strona 44 - 36Metered Rack PDU User Guide

36Metered Rack PDU User GuidephReadingAccess: Administrator, Device UserDescription: View the current, voltage, or power for a phase. Set or view the

Strona 45 - Metered Rack PDU User Guide37

Metered Rack PDU User Guide37prodInfoAccess: Administrator, Device UserDescription: View information about the Rack PDU.Example 1: To view the produc

Strona 46 - 38Metered Rack PDU User Guide

38Metered Rack PDU User GuidetempHighAccess: Administrator, Device UserDescription: Set or view the high-temperature threshold in either Fahrenheit or

Strona 47 - Administrator, Device User

Metered Rack PDU User Guide39whoamiAccess: Administrator, Device UserDescription: View the user name of the active user.Example: apc> whoamiE000: S

Strona 48 - Web Interface

40Metered Rack PDU User GuideWeb InterfaceSupported Web BrowsersYou can use Microsoft® Internet Explorer® (IE) 7.x and higher (on Windows® operating s

Strona 49 - URL address formats

Metered Rack PDU User Guide41URL address formatsType the DNS name or IP address of the Rack PDU in the Web browser’s URL address field and press ENTER

Strona 50 - Web Interface Features

Metered Rack PDU User Guide ivDevice Management... 47About the Device Manager Tab . . . . . . . . .

Strona 51 - Other Web interface features

42Metered Rack PDU User GuideWeb Interface FeaturesRead the following to familiarize yourself with basic Web interface features for your Rack PDU.Tabs

Strona 52 - 44Metered Rack PDU User Guide

Metered Rack PDU User Guide43Quick LinksAt the lower left on each page of the interface, there are three configurable links. By default, the links acc

Strona 53 - Metered Rack PDU User Guide45

44Metered Rack PDU User GuideNetwork Port Sharing on the Web InterfaceGroup Control using Network Port SharingThe web interface of the Rack PDU will h

Strona 54 - About the Home Tab

Metered Rack PDU User Guide45Most of the web pages under the Home, Device Manager, and Environment tabs allow you to switch between Rack PDUs for view

Strona 55 - Device Management

46Metered Rack PDU User GuideAbout the Home TabUse the Home tab to view active alarms, the load status of the Rack PDU, and the most recent Rack PDU e

Strona 56 - Resetting Peak Load and kWh

Metered Rack PDU User Guide47Device ManagementAbout the Device Manager TabPath: Device ManagerUse the Device Manager tab to:• View the load status fo

Strona 57 - Environment

48Metered Rack PDU User GuideConfigure the Name and Location of the Rack PDUPath: Device Manager > Device LoadThe name and location you enter appea

Strona 58 - Use the Event and Data Logs

Metered Rack PDU User Guide49EnvironmentConfigure Temperature and Humidity SensorsPath: EnvironmentThrough the Environment tab, when you have a temper

Strona 59 - Metered Rack PDU User Guide51

50Metered Rack PDU User GuideLogsUse the Event and Data LogsEvent logPath: Logs > Events > optionsYou can view, filter, or delete the event log.

Strona 60 - Data log

Metered Rack PDU User Guide51To filter the log (Logs > Events > log): • Filtering the log by date or time: To display the entire event log, or t

Strona 61 - Metered Rack PDU User Guide53

Metered Rack PDU User Guide vPort Speed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61Ping Response .

Strona 62 - 54Metered Rack PDU User Guide

52Metered Rack PDU User GuideData logPath: Logs > Data > optionsThe data log records the current and power for the device, phase, and banks, as

Strona 63 - Administration: Security

Metered Rack PDU User Guide53To configure data log rotation (Logs > Data > rotation): Set up a password-protected data log repository on a speci

Strona 64 - 56Metered Rack PDU User Guide

54Metered Rack PDU User GuideHow to use FTP or SCP to retrieve log filesAn Administrator or Device User can use FTP or SCP to retrieve a tab-delineate

Strona 65 - Configure the RADIUS Server

Metered Rack PDU User Guide55Administration: SecurityLocal UsersSetting user accessPath: Administration > Security > Local Users > optionsThe

Strona 66 - Inactivity Timeout

56Metered Rack PDU User GuideSelect one of the following:• Local Authentication Only: RADIUS is disabled. Local authentication is enabled.• RADIUS, th

Strona 67 - TCP/IP settings

Metered Rack PDU User Guide57Configure the RADIUS ServerSummary of the configuration procedureYou must configure your RADIUS server to work with the R

Strona 68 - DHCP response options

58Metered Rack PDU User GuideInactivity Timeout Path: Administration > Security > Auto Log OffUse this option to configure the time (3 minutes b

Strona 69 - Ping Response

Metered Rack PDU User Guide59Administration: Network FeaturesTCP/IP and Communication SettingsTCP/IP settings Path: Administration > Network > T

Strona 70 - 62Metered Rack PDU User Guide

60Metered Rack PDU User GuideDHCP response optionsEach valid DHCP response contains options that provide the TCP/IP settings that the Rack PDU needs t

Strona 71 - Metered Rack PDU User Guide63

Metered Rack PDU User Guide61Path: Administration > Network > TCP/IP > IPv6 settingsPort Speed Path: Administration > Network > Port Sp

Strona 72 - Console

Metered Rack PDU User GuideviDevice IP Configuration Wizard ...80Capabilities, Requirements, and Installation . . . .

Strona 73

62Metered Rack PDU User GuideDNS Path: Administration > Network > DNS > optionsUse the options under DNS to configure and test the Domain Nam

Strona 74 - 66Metered Rack PDU User Guide

Metered Rack PDU User Guide63Web Path: Administration > Network > Web > optionsOption Descriptionaccess To activate changes to any of these s

Strona 75 - Metered Rack PDU User Guide67

64Metered Rack PDU User GuideConsole Path: Administration > Network > Console > optionsNote: To use SSH, you must have an SSH client installe

Strona 76 - FTP Server

Metered Rack PDU User Guide65SNMPAll user names, passwords, and community names for SNMP are transferred over the network as plain text. If your netwo

Strona 77 - Administration: Notification

66Metered Rack PDU User GuideSNMPv1 Path: Administration > Network > SNMPv1 > optionsOption Descriptionaccess Enable SNMPv1 Access: Enables S

Strona 78 - 70Metered Rack PDU User Guide

Metered Rack PDU User Guide67SNMPv3 Path: Administration > Network > SNMPv3 > optionsFor SNMP GETs, SETs, and trap receivers, SNMPv3 uses a s

Strona 79 - E-mail notification

68Metered Rack PDU User GuideFTP Server Path: Administration > Network > FTP ServerThe FTP Server settings enable (by default) or disable access

Strona 80 - Setting Description

Metered Rack PDU User Guide69Administration: NotificationEvent Actions Path: Administration > Notification > Event Actions > optionsTypes of

Strona 81 - SNMP Trap Test

70Metered Rack PDU User GuideConfiguring by event. To define event actions for an individual event:1. Select the Administration tab, Notification on t

Strona 82 - Remote Monitoring Service

Metered Rack PDU User Guide71Active, Automatic, Direct NotificationE-mail notificationOverview of setup. Use the Simple Mail Transfer Protocol (SMTP)

Strona 83 - Syslog settings

Metered Rack PDU User Guide viiTroubleshooting ...92Rack PDU Access Problems . . . . . . . .

Strona 84 - Set the Date and Time

72Metered Rack PDU User GuideE-mail test. Path: Administration > Notification > E-mail > testSend a test message to a configured recipient.SM

Strona 85 - Use an .ini File

Metered Rack PDU User Guide73SNMP trapsTrap Receivers. Path: Administration > Notification > SNMP Traps > trap receiversView trap receivers b

Strona 86 - Reset the Rack PDU

74Metered Rack PDU User GuideRemote Monitoring ServicePath: Administration > Notification > Remote MonitoringThe APC Remote Monitoring Service (

Strona 87 - About the Rack PDU

Metered Rack PDU User Guide75Syslog settings. Path: Logs > Syslog > settingsSyslog test and format example. Path: Logs > Syslog > testSend

Strona 88 - Use the Wizard

76Metered Rack PDU User GuideAdministration: General OptionsIdentification Path: Administration > General > IdentificationDefine the Name (the d

Strona 89 - Metered Rack PDU User Guide81

Metered Rack PDU User Guide77Daylight saving Path: Administration > General > Date & Time > daylight savingEnable traditional United Stat

Strona 90 - INI and Network Port Sharing

78Metered Rack PDU User GuideEvent Log and Temperature UnitsPath: Administration > General > PreferencesColor-code event log text This option is

Strona 91 - Detailed procedures

Metered Rack PDU User Guide79Configure Links Path: Administration > General > Quick LinksSelect the Administration tab, General on the top menu

Strona 92 - 84Metered Rack PDU User Guide

80Metered Rack PDU User GuideDevice IP Configuration WizardCapabilities, Requirements, and InstallationHow to use the Wizard to configure TCP/IP setti

Strona 93 - Related Topics

Metered Rack PDU User Guide81Run the Wizard to perform the configuration. To discover and configure the unconfigured Rack PDUs or network-enabled devi

Strona 94 - File Transfers

Metered Rack PDU User Guide1IntroductionProduct FeaturesThe APC by Schneider Electric Metered Rack Power Distribution Unit (PDU) may be used as a stan

Strona 95 - Metered Rack PDU User Guide87

82Metered Rack PDU User GuideHow to Export Configuration SettingsRetrieving and Exporting the .ini FileSummary of the procedureAn Administrator can re

Strona 96 - 88Metered Rack PDU User Guide

Metered Rack PDU User Guide83Detailed proceduresRetrieving. To set up and retrieve an .ini file to export:1. If possible, use the interface of a Rack

Strona 97 - Metered Rack PDU User Guide89

84Metered Rack PDU User GuideTransferring the file to a single Rack PDU. To transfer the .ini file to another Rack PDU, do either of the following:•

Strona 98 - 90Metered Rack PDU User Guide

Metered Rack PDU User Guide85The Upload Event and Error MessagesThe event and its error messagesThe following event occurs when the receiving Rack PDU

Strona 99 - Last Transfer Result codes

86Metered Rack PDU User GuideFile TransfersHow to Upgrade FirmwareBenefits of upgrading firmwareWhen you upgrade the firmware on the Rack PDU:• You o

Strona 100 - Troubleshooting

Metered Rack PDU User Guide87Using the Firmware Upgrade UtilityThis Firmware Upgrade Utility is part of the firmware upgrade package available on the

Strona 101 - Metered Rack PDU User Guide93

88Metered Rack PDU User GuideSCP. To use Secure CoPy (SCP) to upgrade firmware for the Rack PDU, follow these steps (this procedure assumes bootmon do

Strona 102 - 94Metered Rack PDU User Guide

Metered Rack PDU User Guide89How to upgrade multiple Rack PDUsFirmware Upgrade Utility. Use this for multiple firmware updates in IPv4 if you have Win

Strona 103 - Device Command Descriptions

90Metered Rack PDU User GuideIf you are unsure whether to upgrade any particular module, then upgrading all three is recommended.1. Obtain the latest

Strona 104 - 990-3429D-001

Metered Rack PDU User Guide91Verifying Upgrades and UpdatesVerify the success or failure of the transferTo verify whether a firmware upgrade succeeded