APC AP9830 Instrukcje Operacyjne Strona 11

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 24
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 10
7
Configuration
continued
Power-off
condition — DIP
switches #1 &
#2: Table 2
DIP switches 1 and 2 govern the power-off condition for the
Remote Power-Off Device. Refer to the table below to set
DIP switches 1 and 2.
Note
: A contact closure switch toggles between an open and
closed circuit. A voltage input switch applies and
removes a voltage signal. For requirements, see
“Switch types: Table 4” on page 10.
Continued on next page
Switch Type
Position
†0 =
↑,
1 =
Contact Closure
(PINs 2, 5)
Voltage Input
(PINs 3, 4)
DIP
#1
DIP
#2
A normally closed
(N.C.) contact
closure opens
24V is removed
from the voltage
input
10
A normally open
(N.O.) contact
closure closes
24V is applied to the
voltage input
01
INVALID 0 0
INVALID 1 1
Table 2: Power-off condition — DIP switches #1 & #2
Przeglądanie stron 10
1 2 ... 6 7 8 9 10 11 12 13 14 15 16 ... 23 24

Komentarze do niniejszej Instrukcji

Brak uwag