USER’S GUIDE
NetBotz Rack Monitor 200
46
Remote Users
Authentication (Administration>Security>Remote Users>Authentication)
Use this option to select how to administer remote access to this Main Module
.
APC supports the authentication and authorization functions of RADIUS (Remote
Authentication Dial-In User Service).
• When a user accesses the Main Module with RADIUS enabled, an authentication
request is sent to the RADIUS server to determine the user’s permission level.
• RADIUS user names used with the Main Module are limited to 32 characters.
Select one of the following:
• Local Authentication Only: RADIUS is disabled. Local authentication is enabled.
• RADIUS, then Local Authentication: RADIUS and local authentication are enabled.
Authentication is requested from the RADIUS server first. If the RADIUS server fails
to respond, local authentication is used.
• RADIUS Only: RADIUS is enabled. Local authentication is disabled.
For information about local authentication (authentication that can be
administered without the centralized authentication provided by a RADIUS
server), see the Security Handbook provided on the NetBotz Rack Monitor
200 Utility CD and available on the APC Web site at www.apc.com.
If RADIUS Only is selected, and the RADIUS server is unavailable,
improperly identified, or improperly configured, you must use a serial
connection to the control console and change the Access setting to
Local Authentication Only or RADIUS, then Local Authentication to
regain access.