Redpaper
ibm.com/redbooks
Implementing UPS
Configurations with
Microsoft Cluster Server
Hendrik Ernst
Martin Zustak
Peter Fuchs
Silvio Erdenberger
Arwed Tschoeke
Describes how to configure an
uninterruptible power supply in a cluster
Minimize the risks introduced by
UPS failure
Includes CMD files for
streamlined UPS control
Przeglądanie stron 0
1 2 3 4 5 6 ... 95 96

Podsumowanie treści

Strona 1 - Microsoft Cluster Server

Redpaper ibm.com/redbooksImplementing UPS Configurations with Microsoft Cluster ServerHendrik ErnstMartin ZustakPeter FuchsSilvio ErdenbergerArwed Ts

Strona 2

2 Implementing UPS Configurations with Microsoft Cluster Server• UPS monitoring: PowerChute PLUS can monitor only one UPS at a time,independent of the

Strona 3 - March 2001

Chapter 2. APC hardware and software background 3Chapter 2. APC hardware and software backgroundIn the following chapters, we describe some UPS units

Strona 4

4 Implementing UPS Configurations with Microsoft Cluster ServerIn a switching power environment (power supplies in the server), a cos(ϕ)=0.707is assum

Strona 5 - Contents

Chapter 2. APC hardware and software background 5Table 1. Technical specificationsThe typical SU2200RMXLINET on-battery run times versus VA load, in m

Strona 6

6 Implementing UPS Configurations with Microsoft Cluster ServerThe UPS was designed to mount to any standard EIA RS-310 (ANSI C83.9) 19''equ

Strona 7 - © Copyright IBM Corp. 2001 v

Chapter 2. APC hardware and software background 7The UPS is furnished with one input line cord terminated with a CEE7/7 plug andthree 1.8 m long outpu

Strona 8 - Comments welcome

8 Implementing UPS Configurations with Microsoft Cluster ServerFigure 3. APC Smart UPS 3000 — rear viewIn Figure 2 and Figure 3, you can see the APC S

Strona 9 - Chapter 1. The problem

Chapter 2. APC hardware and software background 9The typical SU5000RMINET on-battery run times versus VA load, in minutes areas follows:Table 6. Run t

Strona 10

10 Implementing UPS Configurations with Microsoft Cluster ServerFigure 4. APC Smart UPS 5000 — front viewFigure 5. APC Smart UPS 5000 — rear view2.2 S

Strona 11

Chapter 2. APC hardware and software background 112.2.1 Symmetra Masterframe/MiniframeThe Symmetra is an uninterruptible power array system, designed

Strona 13

12 Implementing UPS Configurations with Microsoft Cluster Server2.2.1.1 Battery sourceThe battery source is comprised of parallel, hot-swappable, 120

Strona 14 - 2.1.2 SU3000RMINET (5U unit)

Chapter 2. APC hardware and software background 13APC part numbers:• SY4KEXI Miniframe with 1 PM (4 kVA) expandable to 8 kVA redundant• SY8KI Minifram

Strona 15 - 3000VA 5 13

14 Implementing UPS Configurations with Microsoft Cluster ServerFor recommendations about Symmetra wiring, see the PDF file at the followingaddress:ht

Strona 16 - 2.1.3 SU5000RMINET

Chapter 2. APC hardware and software background 15Figure 7. AP9607 — APC SmartSlot Interface Expander Card2.3.2 AP9606 Web/SNMP Management CardThe AP9

Strona 17

16 Implementing UPS Configurations with Microsoft Cluster ServerFigure 8. AP9606 — APC Web/SNMP Card2.3.3 Redundant SwitchThe Redundant Switch is a hi

Strona 18 - 2.2 Symmetra

Chapter 2. APC hardware and software background 17The use of a double pole transfer switch by default makes the Redundant Switchfault tolerant. A sing

Strona 19

18 Implementing UPS Configurations with Microsoft Cluster ServerFigure 10. Redundant SwitchFor the Redundant Switch SU044-1 we have a sample solution

Strona 20

Chapter 2. APC hardware and software background 19• User notification of impending shutdown• Power event and data logging• Auto-restart upon power ret

Strona 21 - Table 7. Run time chart

20 Implementing UPS Configurations with Microsoft Cluster Server• Run a command file (an external executable file)• Page users• Send e-mail to notify

Strona 22 - 2.3 UPS options

Chapter 2. APC hardware and software background 21• Comm Lost While On BatteryCommunication with the UPS has been lost while the UPS is on battery. Th

Strona 23

International Technical Support OrganizationImplementing UPS Configurationswith Microsoft Cluster ServerMarch 2001

Strona 24 - 2.3.3 Redundant Switch

22 Implementing UPS Configurations with Microsoft Cluster ServerRECOMMENDED ACTION: Immediately notify the cluster administrator. Usethe notify functi

Strona 25

Chapter 2. APC hardware and software background 23Figure 13. PowerChute PLUS event actions and UPS delays2.4.2 PowerChute network shutdownPowerChute n

Strona 26 - 2.4.1 PowerChute PLUS

24 Implementing UPS Configurations with Microsoft Cluster ServerFigure 14. PowerChute Network shutdown Web interfaceMore information is available at:h

Strona 27

Chapter 2. APC hardware and software background 25More information is available at:http://www.apcc.com/products/accessories/cable_kits.cfm2.5 Power pl

Strona 28

26 Implementing UPS Configurations with Microsoft Cluster ServerFigure 16. Cable D12Figure 17. CableFigure 18. CableIEC 320-C19IEC 320-C14IEC 320-C19C

Strona 29

Chapter 3. UPS configurations for cluster 27Chapter 3. UPS configurations for clusterThere are two different ways to use UPS units:• Single power line

Strona 30

28 Implementing UPS Configurations with Microsoft Cluster Server3.1.1 Timing of UPS actionsFigure 19 shows the timing of UPS actions.Figure 19. Timing

Strona 31 - Total run time available

Chapter 3. UPS configurations for cluster 294. Some commands in UPS.CMD were launched asynchronously. To allow suchoperations to complete, we added a

Strona 32 - 2.4.3 Signaling cables

30 Implementing UPS Configurations with Microsoft Cluster Server• The IBM Netfinity EXP15 storage expansion enclosure (3520) has anelectrical input be

Strona 33 - IEC 320-C14

Chapter 3. UPS configurations for cluster 31administrator intervention is useful to analyze the status of such componentsbefore starting production sy

Strona 34 - Figure 18. Cable

© Copyright International Business Machines Corporation 2001. All rights reserved.Note to U.S Government Users - Documentation related to restricted

Strona 35 - Important

32 Implementing UPS Configurations with Microsoft Cluster ServerWe recommend that you attach each server to one UPS and then connect eachshared storag

Strona 36 - 3.1.1 Timing of UPS actions

Chapter 3. UPS configurations for cluster 333.2.1 Control flow in UPS.CMDIn the event of a UPS power loss, a delay (UPS On Battery Delay) is set. Afte

Strona 37 - 3.1.2 UPS capacity planning

34 Implementing UPS Configurations with Microsoft Cluster ServerThe operating system shutdown is started from the command file, not by usingthe PowerC

Strona 38

Chapter 3. UPS configurations for cluster 35PLUS on the node with a black serial cable” on page 35 and 3.2.6, “InstallingPowerChute PLUS on the node w

Strona 39

36 Implementing UPS Configurations with Microsoft Cluster Server2. Select the Custom option and click Next. This displays Figure 26.Figure 26. Install

Strona 40

Chapter 3. UPS configurations for cluster 37Figure 28. Install PowerChute PLUS — automatically detect UPS5. The window shown in Figure 28 will be disp

Strona 41 - 3.2.1 Control flow in UPS.CMD

38 Implementing UPS Configurations with Microsoft Cluster Server.Figure 30. Install PowerChute PLUS — remote monitoring8. In this window select the bo

Strona 42 - 3.2.3 Preparing both nodes

Chapter 3. UPS configurations for cluster 392. Select your server. In our scenario, the second node is the NF8500R with theblack serial cable. Click t

Strona 43 - Figure 24. Directory view

40 Implementing UPS Configurations with Microsoft Cluster Server– UPS Turn Off Delay: This period of time begins at power loss. After thisinterval, th

Strona 44

Chapter 3. UPS configurations for cluster 41Figure 35. Single UPS Run Command File — UPS On Battery8. In the Event Actions window, select UPS On Batte

Strona 45

© Copyright IBM Corp. 2001 iiiContentsPreface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Strona 46

42 Implementing UPS Configurations with Microsoft Cluster ServerFigure 36. Single UPS Run Command File — Low Battery Condition9. Now select Low Batter

Strona 47

Chapter 3. UPS configurations for cluster 43Figure 37. Single UPS Event Actions10.In the Event Actions window, select PowerChute PLUS Started.Clear th

Strona 48

44 Implementing UPS Configurations with Microsoft Cluster Server11.In the Event Actions window shown in Figure 38, select Comm Lost While OnBattery.a.

Strona 49

Chapter 3. UPS configurations for cluster 45Figure 40. Install PowerChute PLUS — Select Components to Install3. Select the boxes of the components you

Strona 50

46 Implementing UPS Configurations with Microsoft Cluster ServerFigure 42. Install PowerChute PLUS — automatically detect UPS parameters7. The UPS wil

Strona 51

Chapter 3. UPS configurations for cluster 47Figure 44. Disable remote monitoring9. In this window, select the box to enable the PowerChute PLUS remote

Strona 52

48 Implementing UPS Configurations with Microsoft Cluster Server2. Select your server. In our scenario, the first node is the NF8500L with the greyser

Strona 53

Chapter 3. UPS configurations for cluster 49Figure 48. Single UPS Run Command File — UPS On Battery6. In the Event Actions window, select UPS On Batte

Strona 54

50 Implementing UPS Configurations with Microsoft Cluster ServerFigure 49. Single UPS Run Command File — Low Battery Condition7. In the Event Actions

Strona 55

Chapter 3. UPS configurations for cluster 518. Select PowerChute PLUS Started.Clear the Run Command File checkbox.We strongly recommend that you do no

Strona 56

iv Implementing UPS Configurations with Microsoft Cluster Server4.4 StartUp Parameter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Strona 57

52 Implementing UPS Configurations with Microsoft Cluster ServerFigure 51. Multiple UPS units with Redundant SwitchUPS fault tolerance is provided by

Strona 58

Chapter 3. UPS configurations for cluster 53Figure 52. Two UPS units without application handlingBut connecting the power cords in this way prevents c

Strona 59

54 Implementing UPS Configurations with Microsoft Cluster ServerFigure 53. Two UPS units with application handlingThis setup looks very similar to Fig

Strona 60

Chapter 3. UPS configurations for cluster 55What should a node do with cluster resources that are owned at the time of apower loss?If the other node i

Strona 61

56 Implementing UPS Configurations with Microsoft Cluster ServerFigure 54. Double UPS flowchartThe flowchart shown in Figure 54 has three branches. Th

Strona 62

Chapter 3. UPS configurations for cluster 57The three failure scenarios in 3.3, “Solutions with double power lines” on page 51are handled as follows:1

Strona 63 - 3.3.3 Control flow in UPS.CMD

58 Implementing UPS Configurations with Microsoft Cluster Serverboth APC SMART-UPS 5000 for redundancy. The hubs are connected only to oneAPC SMART-UP

Strona 64

Chapter 3. UPS configurations for cluster 59Figure 57. Install PowerChute PLUS — choose type of installation1. Select the Custom option and click Next

Strona 65 - Figure 55. Double UPS

60 Implementing UPS Configurations with Microsoft Cluster ServerFigure 59. Install PowerChute PLUS — automatic shutdown components3. Do not check any

Strona 66 - Figure 56. Directory view

Chapter 3. UPS configurations for cluster 61Figure 61. Install PowerChute PLUS — automatically detect the UPS6. Your UPS has been discovered correctly

Strona 67

© Copyright IBM Corp. 2001 vPrefaceThis redpaper is the product of a collaboration of specialists from American Power Conversion, Inc. (APC), Computer

Strona 68

62 Implementing UPS Configurations with Microsoft Cluster Server1. Start PowerChute PLUS. You see a window (shown in Figure 63) with allservers in the

Strona 69

Chapter 3. UPS configurations for cluster 63Figure 65. UPS Shutdown Parameters window4. On the Shutdown Parameters window, enter the following paramet

Strona 70

64 Implementing UPS Configurations with Microsoft Cluster ServerFigure 66. Double UPS Application Shutdown Parameters window6. Disable the application

Strona 71

Chapter 3. UPS configurations for cluster 65Figure 68. Double UPS Run Command File — Low Battery Condition9. In the Event Actions window, select Low B

Strona 72

66 Implementing UPS Configurations with Microsoft Cluster ServerClear the check in the Run Command File checkbox.We strongly recommend that you do not

Strona 73

Chapter 4. The command file UPS.CMD 67Chapter 4. The command file UPS.CMDAll actions necessary for shutting down a node in the cluster are performed b

Strona 74

68 Implementing UPS Configurations with Microsoft Cluster ServerIn lines 49 and 50, the environment variable for the computer name is comparedwith var

Strona 75 - Attention

Chapter 4. The command file UPS.CMD 69094 CLUSTER.EXE %TheOtherNodeName% NODE %TheOtherNodeName% | FIND "Up"The result of this check is requ

Strona 76 - 4.2 Parameter UPSOnBattery

70 Implementing UPS Configurations with Microsoft Cluster Server/MOVETO initiates moving of a resource to the node specified. Note that we don’tadd a

Strona 77 - 4.2.1 MoveClusterGroups

Chapter 4. The command file UPS.CMD 71According to recommendations from Microsoft, there should no applicationresources belonging to the Cluster Group

Strona 78 - 4.2.2 GroupOffline

vi Implementing UPS Configurations with Microsoft Cluster ServerComments welcomeYour comments are important to us!We want our redpapers to be as help

Strona 79

72 Implementing UPS Configurations with Microsoft Cluster ServerA parameter value SingleUPSOnBattery means a configuration with one UPS.This is explai

Strona 80 - 4.4 StartUp Parameter

Appendix A. Downloading the additional material 73Appendix A. Downloading the additional materialThe programs and CMD files shown in Appendix B, “UPS.

Strona 81 - File name Description

74 Implementing UPS Configurations with Microsoft Cluster Server1. In the PowerChute PLUS main window, select Configuration > EventActions.2. In th

Strona 82 - A.2.2 Windows 2000

Appendix A. Downloading the additional material 75A hint for Windows 2000 users: The quorum resource is no longer in a separateresource group. It is n

Strona 83

76 Implementing UPS Configurations with Microsoft Cluster Server

Strona 84

Appendix B. UPS.CMD 77Appendix B. UPS.CMD001 @ECHO OFF002 REM ***************************************************************************003 REM004 RE

Strona 85 - Appendix B. UPS.CMD

78 Implementing UPS Configurations with Microsoft Cluster Server058 IF %1 == UPSOnBattery GOTO UPSOnBattery059 IF %1 == SingleUPSOnBattery GOTO Si

Strona 86

Appendix B. UPS.CMD 79118 REM Move groups to the other node119120 REM !!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!12112

Strona 87 - Appendix B. UPS.CMD 79

80 Implementing UPS Configurations with Microsoft Cluster Server176177178 REM ------------------------------------------------------------------------

Strona 88

Appendix C. DELAY3.EXE source 81Appendix C. DELAY3.EXE source{************************************************}{ Delay3 tool

Strona 89 - Appendix C. DELAY3.EXE source

© Copyright IBM Corp. 2001 1Chapter 1. The problemHow can servers be protected against power failures? Usually redundant powersupplies and redundant p

Strona 90

82 Implementing UPS Configurations with Microsoft Cluster Server StopSeconds:=Second + DelaySeconds; Temp := 0; if StopSeco

Strona 91

Appendix C. DELAY3.EXE source 83 writeln('* where xxx are the seconds that should be waited. *');

Strona 92

84 Implementing UPS Configurations with Microsoft Cluster Server

Strona 93

Appendix D. Referenced documents 85Appendix D. Referenced documents•IBM Netfinity 8500R Hardware Maintenance Manual(8681-4RY, 4RG, 5RY,5RG, 6RY, and 6

Strona 94

86 Implementing UPS Configurations with Microsoft Cluster Server

Strona 95 - Appendix E. Special notices

© Copyright IBM Corp. 2001 87Appendix E. Special noticesThis publication is intended to help customers implement uninterruptible power supplies in a