Operation and
Maintenance
InRow
®
RD
ACRD500
ACRD501
ACRD502
Przeglądanie stron 0
1 2 3 4 5 6 ... 59 60

Podsumowanie treści

Strona 1 - Maintenance

Operation andMaintenanceInRow® RDACRD500ACRD501ACRD502

Strona 2 - 동봉된 CD 안에 한국어 매뉴얼이 있습니다

InRow RD Operation and Maintenance2Safety Read and adhere to the following important safety considerations when working with this cooling unit.Note: A

Strona 3

3InRow RD Operation and MaintenanceCommissioningWarning: Procedures in this section must be performed by APC authorized personnel.Electrical Hazard: P

Strona 4

InRow RD Operation and Maintenance4Electrical Inspection ChecklistThe electrical inspection verifies that all electrical connections are secure and co

Strona 5 - Contents

5InRow RD Operation and MaintenanceMechanical Inspection ChecklistThe mechanical inspection verifies that all mechanical components and connections ar

Strona 6

InRow RD Operation and Maintenance6User Interface Inspection ChecklistThe user interface inspection verifies that the sensors and internal communicati

Strona 7

7InRow RD Operation and MaintenanceStart-up Inspection ChecklistThe start-up inspection ensures that the equipment is operating properly after the ini

Strona 8

InRow RD Operation and Maintenance8Final Inspection ChecklistThe final inspection verifies that the system is clean, the installed options work proper

Strona 9 - General Information

9InRow RD Operation and MaintenanceCharging With RefrigerantCalculating R407C chargeUse the following table and formula when calculating the total R40

Strona 10

InRow RD Operation and Maintenance10Charging the equipmentCaution: This procedure is to be done by APC-trained personnel only.R407C is a blend refrige

Strona 11 - Commissioning

11InRow RD Operation and Maintenance8. Charge the rest of the calculated liquid refrigerant very slowly through the suction port.9. Verify that the si

Strona 12

This manual is available in English on the enclosed CD.Dieses Handbuch ist in Deutsch auf der beiliegenden CD-ROM verfügbar.Deze handleiding staat in

Strona 13

InRow RD Operation and Maintenance12Compressor Oil ChargeCaution: This procedure is to be done by APC-trained personnel only.You may need to add oil t

Strona 14 - Ensure that:

13InRow RD Operation and Maintenance3. Purge the pump and hose:a. Ensure that the oil pump is clean. Insert the pump in the oil container and make sur

Strona 15 - Start-up Inspection Checklist

InRow RD Operation and Maintenance14OperationDisplay Interface Item Function1 Critical Alarm LED (red) When lit, a critical alarm condition exists and

Strona 16 - Final Inspection Checklist

15InRow RD Operation and MaintenanceUsing the DisplayEvery time you apply power to the cooling unit, the display interface initializes, causing the LE

Strona 17 - Charging With Refrigerant

InRow RD Operation and Maintenance16Navigating the main menuSelector arrow. Press the up or down arrow key to move the selector arrow  to a main menu

Strona 18 - Charging the equipment

17InRow RD Operation and MaintenanceUsing the Path statementSelect the main- and sub-menu options specified in the path statement to view or configure

Strona 19

InRow RD Operation and Maintenance18Start the cooling unitPath: Main > On/StandbyTo start the cooling unit, change the setting to On by pressing th

Strona 20 - Compressor Oil Charge

19InRow RD Operation and MaintenanceGeneral ConfigurationThe cooling group configuration options are set during the commissioning of the cooling units

Strona 21

InRow RD Operation and Maintenance20ContactsView the state of Input and output contactsPath: Main > Configure Unit > Discrete I/OEach cooling un

Strona 22 - Operation

21InRow RD Operation and MaintenanceType. Set the rack deployment strategy for the cooling units of this cooling group.• In-Row: Air flow is not ducte

Strona 23 - Using the Display

American Power Conversion Legal DisclaimerThe information presented in this manual is not warranted by the American Power Conversion Corporation to be

Strona 24 - Format: dd/mm/yyyy

InRow RD Operation and Maintenance22Control the EnvironmentThe primary function of the cooling unit is to cool air from the hot aisle and deliver it t

Strona 25 - Password entry

23InRow RD Operation and Maintenance• Fan Spd: .Set the fan speed preference that will give you the desired temperature difference (DT). Each fan spee

Strona 26 - Path: Main > On/Standby

InRow RD Operation and Maintenance24Tune the PID loopTune the PID loop to optimize the performance of the cooling group. Caution: This procedure must

Strona 27 - Capacity

25InRow RD Operation and MaintenanceRun hoursThe cooling unit records the number of hours each of its components has operated. When a component is rep

Strona 28 - Cooling Group Configuration

InRow RD Operation and Maintenance26Display Set display interface settings, including time and date, units, passwords, and time-out. You can also adju

Strona 29 - Configure Modbus

27InRow RD Operation and MaintenanceAdjust displayPath: Main Menu >Configure Display Contrast. Adjust the visibility of the screen text. Lower numb

Strona 30 - Control the Environment

InRow RD Operation and Maintenance28Network ConfigurationThe cooling unit is shipped with a Network Management Card (NMC) that enables you to manage t

Strona 31 - PID settings

29InRow RD Operation and MaintenanceView Status ReadingsThe display interface has several options for viewing the status of the cooling unit, the cool

Strona 32 - Tune the PID loop

InRow RD Operation and Maintenance30Compressor Drive: Voltage. The compressor voltage.Compressor Drive: Current. The compressor current draw.Compresso

Strona 33 - Service intervals

31InRow RD Operation and MaintenanceEvent LogThe event log saves status information and a message each time a change in the cooling group is detected.

Strona 35 - Display units

InRow RD Operation and Maintenance32Alarm messages and suggested actionsAlarm Message Severity Action RequiredAir Containment Pressure Sensor FaultWar

Strona 36 - MAC Address

33InRow RD Operation and MaintenancePersistant High Discharge Pressure FaultCritical • Indicates there were three High Discharge Pressure shutdowns in

Strona 37 - View Status Readings

InRow RD Operation and Maintenance34Network Management CardQuick ConfigurationThe cooling unit is shipped with a Network Management Card that enables

Strona 38 - About the cooling unit

35InRow RD Operation and Maintenance2. If autorun is enabled, the user interface of the CD starts when you insert the CD. If autorun is not enabled, o

Strona 39 - Path: Main > Clear Alarms

InRow RD Operation and Maintenance36DHCP. You can use a RFC2131/RFC2132-compliant DHCP server to configure the TCP/IP settings for the Network Managem

Strona 40

37InRow RD Operation and MaintenanceRemote access to the control consoleFrom any computer on the same subnet as the Network Management Card, you can u

Strona 41

InRow RD Operation and Maintenance38Control consoleAfter you log on at the control console, as described in“Local access to the control console” on pa

Strona 42 - Network Management Card

39InRow RD Operation and MaintenanceAccess a Configured Network Management CardOverviewAfter the Network Management Card is running on your network, y

Strona 43 - .ini file utility

InRow RD Operation and Maintenance40Telnet for basic access. Telnet provides the basic security of authentication by user name and password, but not t

Strona 44 - 04) is the length

41InRow RD Operation and MaintenanceFTP/SCPYou can use FTP (enabled by default) or Secure CoPy (SCP) to transfer downloaded firmware to the Network Ma

Strona 45

ContentsInRow RD Operation and Maintenance iGeneral Information... 1Overview . . . . . . . . . .

Strona 46 - Control console

InRow RD Operation and Maintenance42Recover From a Lost PasswordYou can use a local computer (a computer that connects to the Network Management Card

Strona 47 - Telnet and SSH

43InRow RD Operation and MaintenanceMaintenanceMonthly Preventive MaintenancePhotocopy the following pages and use them during the maintenance procedu

Strona 48

MechanicalElectrical Hazard: Turn off the cooling unit and disconnect all power sources. Perform Lockout/Tagout procedures before performing any elect

Strona 49

45InRow RD Operation and MaintenanceQuarterly Preventive Maintenance* Perform all the Monthly Preventive Maintenance items and the items below.Prepare

Strona 50 - Recover From a Lost Password

InRow RD Operation and Maintenance46TroubleshootingProblem Possible Cause Corrective ActionControls erratic or inoperative• Inlet temperature to cool

Strona 51

47InRow RD Operation and MaintenanceAlarms do not show up on monitoring equipment (Customer Output Contact)• External monitoring equipment is not rece

Strona 52 - Electrical

InRow RD Operation and Maintenance48WarrantyOne-Year Factory WarrantyThe limited warranty provided by American Power Conversion (APC®) in this Stateme

Strona 53 - Cleanliness

49InRow RD Operation and MaintenanceIN NO EVENT SHALL APC, ITS OFFICERS, DIRECTORS, AFFILIATES OR EMPLOYEES BE LIABLE FOR ANY FORM OF INDIRECT, SPECIA

Strona 54 - Troubleshooting

InRow RD Operation and Maintenance50Warranty ProceduresClaimsTo obtain service under the warranty, contact APC Customer Support (see the back cover of

Strona 56 - Warranty

InRow RD Operation and Maintenance iiContacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20View th

Strona 57 - Warranty claims

02/2008990-3234-001*990-3234-001*APC Worldwide Customer SupportCustomer support for this or any other APC product is available at no charge in any of

Strona 58 - Warranty Procedures

InRow RD Operation and Maintenance iiiNetwork Management Card ...34Quick Configuration . . . . . . . . . . . .

Strona 59

InRow RD Operation and Maintenance ivTroubleshooting ..... 46Warranty...

Strona 60 - *990-3234-001*

1InRow RD Operation and MaintenanceGeneral InformationOverviewNote the definitions for the icons here and be observant for them throughout this manual