ATS with Power
Distribution
InfraStruXure Power
Generation System
Operation Manual
Przeglądanie stron 0
1 2 3 4 5 6 ... 101 102

Podsumowanie treści

Strona 1 - Distribution

ATS with PowerDistributionInfraStruXure PowerGeneration SystemOperation Manual

Strona 3 - About This Manual

*990-1845A*APC Worldwide Customer SupportCustomer support for this or any other APC product is available at no charge in any of the following ways:• V

Strona 4

List of Graphics for 990-18451gen0514b.cdr ipg0002a.cdr 5pg0031a.cdr 6pg0032a.cdr 7pg0078a.cdr, pg0079a.cdr, pg0081a.cdr 7pg0082a.cdr 8pg0083a.cdr 8pg

Strona 5 - Contents

List of Graphics for 990-18452pg0039a.cdr 63pdx0206a.cdr 63pdx0206a.cdr 63pdx0202a.cdr 64pdx0203a.cdr 64pdx0204a.cdr 64pdx0205a.cdr 64pg0061a.cdr 67pg

Strona 6

Automatic Transfer Switch with Power Distribution 1SafetyOverviewSave these instructionsThis manual contains important instructions that must be follo

Strona 7

2 Automatic Transfer Switch with Power DistributionWarningsThe components in the InfraStruXure Power Generation System and UPS power distribution syst

Strona 8

Safety: WarningsAutomatic Transfer Switch with Power Distribution 3InstallationInstall this ATS in accordance to the National Electrical Code (NFPA 75

Strona 10

Automatic Transfer Switch with Power Distribution 5OverviewInfraStruXure Power Generation SystemThe InfraStruXure Power Generation System consists of

Strona 11 - Overview

6 Automatic Transfer Switch with Power DistributionHow the InfraStruXure Power Generation System OperatesOperation of the ATS during a utility mains f

Strona 12 - Warnings

Overview: How the InfraStruXure Power Generation System OperatesAutomatic Transfer Switch with Power Distribution 7Generator start sequenceThe generat

Strona 13 - See also

Overview: How the InfraStruXure Power Generation System Operates8 Automatic Transfer Switch with Power DistributionOpen and closed transfersWhen a tra

Strona 14

Overview: How the InfraStruXure Power Generation System OperatesAutomatic Transfer Switch with Power Distribution 9Fuel monitoring/runtime calculation

Strona 17 - Generator cool-down

Automatic Transfer Switch with Power Distribution 11ATS with Power Distribution Front view, door closedTwenty knockouts are provided on the roof, the

Strona 18 - Source 1 Neutral Source 2

Overview: ATS with Power Distribution12 Automatic Transfer Switch with Power DistributionFront view, door openThe dead front provides access to the p

Strona 19

Overview: ATS with Power DistributionAutomatic Transfer Switch with Power Distribution 13ATS panel board, left sideThe handle aids the removal of the

Strona 20

Overview: ATS with Power Distribution14 Automatic Transfer Switch with Power DistributionATS panel board, right sideInput conductors from the utility

Strona 21 - ATS with Power Distribution

Automatic Transfer Switch with Power Distribution 15ATS Component DetailsMotorized switchesThe operating lever indicates the present position of the

Strona 22 - Front view, door open

Overview: ATS Component Details16 Automatic Transfer Switch with Power DistributionAutomatic operation control panelFor a discussion of Automatic Oper

Strona 23 - ATS panel board, left side

Overview: ATS Component DetailsAutomatic Transfer Switch with Power Distribution 17ATS monitoring unitThis port connects to the Source 2 volt-sensing

Strona 24 - ATS panel board, right side

Overview: ATS Component Details18 Automatic Transfer Switch with Power DistributionATS label kitATS Label—Place this label on the outside of the ATS e

Strona 25 - ATS Component Details

Automatic Transfer Switch with Power Distribution 19OperationAutomatic OperationHow to place the InfraStruXure Power Generation System in automatic op

Strona 26 - User connection plate

Automatic Transfer Switch with Power Distribution iAbout This ManualAudienceThis manual is intended for end-users of the InfraStruXure Automatic Trans

Strona 27 - ATS monitoring unit

Operation: Automatic Operation20 Automatic Transfer Switch with Power DistributionHow to reset automatic operation on the ATS and on the generatorRese

Strona 28 - ATS label kit

Operation: Automatic OperationAutomatic Transfer Switch with Power Distribution 21Problem—loss of automatic operationTypically, the Not In Automatic O

Strona 29 - Operation

22 Automatic Transfer Switch with Power DistributionEmergency Manual OperationWarning—before you operate the ATS manuallyThe procedures in this sectio

Strona 30

Operation: Emergency Manual OperationAutomatic Transfer Switch with Power Distribution 23How to power the load from the generator1. Place the ATS Auto

Strona 31

Operation: Emergency Manual Operation24 Automatic Transfer Switch with Power Distribution5. Turn the Source 2 switch to ON ():a. Set the selector swi

Strona 32 - Emergency Manual Operation

Operation: Emergency Manual OperationAutomatic Transfer Switch with Power Distribution 25How to return to powering the load from utility mains1. Ensur

Strona 33

Operation: Emergency Manual Operation26 Automatic Transfer Switch with Power Distribution5. Turn off the generator by following this procedure:a. Ensu

Strona 34

Automatic Transfer Switch with Power Distribution 27Total Power Off To reduce risk of electric shock or injury to persons, disconnect all sources of s

Strona 35

Operation: Total Power Off28 Automatic Transfer Switch with Power Distribution3. Set the Source 2 switch on the ATS to OFF ():a. Set the selector swi

Strona 36 - /Manual/Auto

Automatic Transfer Switch with Power Distribution 29Display InterfaceOverviewYou can use the display interface to configure settings, set alarm thresh

Strona 38 - Operation: Total Power Off

Display Interface: Overview30 Automatic Transfer Switch with Power DistributionTop-level status screensAfter displaying a brief start-up screen after

Strona 39 - Display Interface

Display Interface: OverviewAutomatic Transfer Switch with Power Distribution 31Navigating through screensTo open any screen, press the Up and Down arr

Strona 40 - NTER key when the selector

32 Automatic Transfer Switch with Power DistributionLoad-MeterTotal Load by PhaseTotal Load SummaryPower FactorTotal Load by PhaseTotal Load SummaryPo

Strona 41 - Password-protected screens

Automatic Transfer Switch with Power Distribution 33ATS/VoltageATS PositionS1-UtilityATS Position: S1S1-Utility: OKS2-Generator: OFFATS SetupOne of th

Strona 42 - Load-Meter

Display Interface: ATS/Voltage34 Automatic Transfer Switch with Power DistributionS2-GeneratorOne of the following is displayed to describe the condit

Strona 43 - ATS/Voltage

Display Interface: ATS/VoltageAutomatic Transfer Switch with Power Distribution 35ATS SetupPress the ENTER key when the selector arrow rests at the AT

Strona 44 - S2-Generator

Display Interface: ATS/Voltage36 Automatic Transfer Switch with Power DistributionATS Blocking • Transfer Blocking: Defines conditions that will preve

Strona 45 - ATS Setup

Automatic Transfer Switch with Power Distribution 37GeneratorGenerator StatusGenerator StatusFuel & RuntimeStatistics & Maint.Generator Settin

Strona 46

Display Interface: Generator38 Automatic Transfer Switch with Power Distribution• Maintenance Record: Scroll through a list of items that accumulate a

Strona 47 - Generator

Automatic Transfer Switch with Power Distribution 39TestingView Test LogRun/View TestView Test LogRun/View TestTest ScheduleTest DurationDisplays all

Strona 48

ContentsAutomatic Transfer Switch with Power Distribution iiiSafety ...1Overview .

Strona 49 - Test Duration

Display Interface: Testing40 Automatic Transfer Switch with Power DistributionTest ScheduleTest DurationUse this menu to schedule a test in the future

Strona 50 - Load Test: Monthly

Display Interface: TestingAutomatic Transfer Switch with Power Distribution 41How a test occursWhen a test is not in progress, the ATS is waiting for

Strona 51 - How a test occurs

42 Automatic Transfer Switch with Power DistributionStatsStatistics: 00 of 00XX,XXXXResetReset AllName of statistic here Scroll through a list of item

Strona 52 - NTER key and

Automatic Transfer Switch with Power Distribution 43AlarmsView Active AlarmsView a list of all alarms that exist presently. When an alarm is present,

Strona 53 - Alarm Beeper

Display Interface: Alarms44 Automatic Transfer Switch with Power DistributionAlarm BeeperClearing latched alarmsWhen an alarm is present, the ATS disp

Strona 54 - Clearing latched alarms

Automatic Transfer Switch with Power Distribution 45ConfigSystem/NetworkSystem/NetworkContacts & RelaysSub-Feed Config.Factory DefaultsManufacture

Strona 55 - System/Network

Display Interface: Config46 Automatic Transfer Switch with Power DistributionContacts & RelaysThe ATS can monitor external contact closure events.

Strona 56 - Contacts & Relays

Display Interface: ConfigAutomatic Transfer Switch with Power Distribution 47Electrical ConfigFactory DefaultsManufacturer DataSystem IDThe following

Strona 58

Automatic Transfer Switch with Power Distribution 49Communication ConfigurationATS Management OptionsOverviewYou have two management options for the A

Strona 59 - Communication Configuration

iv Automatic Transfer Switch with Power DistributionATS Component Details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15Motorized swit

Strona 60

50 Automatic Transfer Switch with Power DistributionConfiguring the InfraStruXure ManagerConnect the ATS to the InfraStruXure Manager1. Connect a Cat-

Strona 61 - Interface

Automatic Transfer Switch with Power Distribution 51Configuring the ATS Network Management InterfaceConnect the ATS to your network1. Connect a Cat-5

Strona 62

Communication Configuration: Configuring the ATS Network Management Interface52 Automatic Transfer Switch with Power DistributionConfiguration Overvie

Strona 63

Communication Configuration: Configuring the ATS Network Management InterfaceAutomatic Transfer Switch with Power Distribution 53BOOTP & DHCP conf

Strona 64

Communication Configuration: Configuring the ATS Network Management Interface54 Automatic Transfer Switch with Power DistributionDHCP. You can use a R

Strona 65

Communication Configuration: Configuring the ATS Network Management InterfaceAutomatic Transfer Switch with Power Distribution 55Local access to the c

Strona 66 - from the Network menu

Communication Configuration: Configuring the ATS Network Management Interface56 Automatic Transfer Switch with Power Distribution– LINUX command forma

Strona 67 - Management Interface

Automatic Transfer Switch with Power Distribution 57How to Access the ATS Network Management InterfaceWeb interface As your browser, you can use Micro

Strona 68

Communication Configuration: How to Access the ATS Network Management Interface58 Automatic Transfer Switch with Power DistributionTelnet and SSHYou c

Strona 69

Communication Configuration: How to Access the ATS Network Management InterfaceAutomatic Transfer Switch with Power Distribution 59FTP and SCPYou can

Strona 70 - Management Interface Password

Automatic Transfer Switch with Power Distribution vTesting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39View

Strona 71 - Relay Outputs to the ATS

60 Automatic Transfer Switch with Power DistributionHow to Recover From a Lost Network Management Interface Password1. Select a serial port at the loc

Strona 72 - NTER key

Automatic Transfer Switch with Power Distribution 61Customizing and Updating the ATSHow to Connect User Input Contacts and Relay Outputs to the ATSOve

Strona 73

Customizing and Updating the ATS: How to Connect User Input Contacts and Relay Outputs to the ATS62 Automatic Transfer Switch with Power DistributionH

Strona 74 - MADE IN USA

Automatic Transfer Switch with Power Distribution 63How to Connect an EPO Switch to the ATSOverviewConnecting the switch. The Emergency Power Off (EPO

Strona 75 - Active Alarm xxofxx

Customizing and Updating the ATS: How to Connect an EPO Switch to the ATS64 Automatic Transfer Switch with Power DistributionConnect an EPO switch to

Strona 76 - Safety warnings

Customizing and Updating the ATS: How to Connect an EPO Switch to the Automatic Transfer Switch with Power Distribution 653. Test the EPO switch to en

Strona 77

Customizing and Updating the ATS: How to Connect an EPO Switch to the ATS66 Automatic Transfer Switch with Power DistributionSafety warningsHazardous

Strona 78 - Circuit Breakers to the ATS

Automatic Transfer Switch with Power Distribution 67How to Allow Easy Access to the ATS Display InterfaceThe front door of the ATS has a Plexiglas pla

Strona 79

68 Automatic Transfer Switch with Power DistributionHow to Add Sub-Feed Output Distribution Circuit Breakers to the ATSOutput distribution circuit bre

Strona 80

Customizing and Updating the ATS: How to Add Sub-Feed Output Automatic Transfer Switch with Power Distribution 69Determine the configuration of the pa

Strona 81

vi Automatic Transfer Switch with Power DistributionHow to Access the ATS Network Management Interface. . . . . . 57Web interface . . . . . . . . . .

Strona 82

Customizing and Updating the ATS: How to Add Sub-Feed Output Distribution Circuit Breakers to the ATS70 Automatic Transfer Switch with Power Distribut

Strona 83

Customizing and Updating the ATS: How to Add Sub-Feed Output Automatic Transfer Switch with Power Distribution 71Parts and tools needed for installati

Strona 84

Customizing and Updating the ATS: How to Add Sub-Feed Output Distribution Circuit Breakers to the ATS72 Automatic Transfer Switch with Power Distribut

Strona 85 - Specifications

Automatic Transfer Switch with Power Distribution 73How to Download Firmware UpdatesThe InfraStruXure ATS with Power Distribution requires multiple fi

Strona 87

Automatic Transfer Switch with Power Distribution 75SpecificationsATS with Power DistributionElectrical Current Rating 250AVoltage Class 480VACVolta

Strona 88

Specifications: ATS with Power Distribution76 Automatic Transfer Switch with Power DistributionInstallation and Wiring 208V 480VMaximum Utility Mains

Strona 89 - Warranty

Specifications: ATS with Power DistributionAutomatic Transfer Switch with Power Distribution 77EnvironmentalOperating Temperature Range 23 to 104°F /

Strona 91 - Life-Support Policy

Automatic Transfer Switch with Power Distribution 79Warranty, Life-Support Policy, and ServiceWarrantyAPC warrants that all components of the InfraStr

Strona 92 - How to contact APC

Automatic Transfer Switch with Power Distribution viiAppendix A: Custom Installations ...83If Source 2 is a Second Utility Mai

Strona 93 - Connection

Warranty, Life-Support Policy, and Service: Warranty80 Automatic Transfer Switch with Power DistributionTHERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, B

Strona 94 - InfraStruXure Generator

Automatic Transfer Switch with Power Distribution 81Life-Support PolicyAmerican Power Conversion Corporation (APC) and its affiliates and subsidiaries

Strona 95

82 Automatic Transfer Switch with Power DistributionServiceHow to contact APCCustomer support for this or any other APC product is available at no cha

Strona 96

Automatic Transfer Switch with Power Distribution 83Appendix A: Custom InstallationsIf Source 2 is a Second Utility Mains ConnectionDifferences in you

Strona 97

84 Automatic Transfer Switch with Power DistributionIf Source 2 is a Generator that is Not an APC InfraStruXure GeneratorDifferences in your system fr

Strona 98

IndexAutomatic Transfer Switch with Power Distribution 85AAccess panel, on panel board, 13–14Accessing the display interface, 67Agency approvals, 77Al

Strona 99 - Radio Frequency Interference

86 Automatic Transfer Switch with Power DistributionGenerator, non-APC, 84Get set on LED, 29HHandle, on panel board, 13Humidity, for operation, 3IInfr

Strona 100 - *990-1845A*

Automatic Transfer Switch with Power Distribution 87Source 1 control transformer, location of, 13Source 1 current transformer, location of, 14Source 1

Strona 102

Radio Frequency InterferenceUSA—FCCThis equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 1