Page 13 10/05/09
1. Test and adjust controls and safeties. Replace damaged or malfunctioning controls and
equipment.
2. Train the Owner’s maintenance personnel on procedures and schedules related to start-up
and shutdown, troubleshooting, servicing, and preventive maintenance.
3. Review data in operation and maintenance manuals with the Owner’s personnel.
4. Schedule training with the Owner, through the Architect/Engineer, with at least seven day’s
advanced notice.
B. UPS Training Workshop: A UPS training workshop shall be available from the UPS manufacturer.
The training workshop shall include, but shall not be limited to, a combination of lecture and
practical instruction with hands-on laboratory sessions. The training workshop shall include, but
shall not be limited to, instruction about safety procedures, UPS operational theory, sub-assembly
identification and operation, system controls, adjustments, preventative maintenance, and
troubleshooting.
3.5 PROTECTION
A. Provide final protection and maintain conditions in a manner acceptable to the Installer, that shall
ensure that the solid state UPS shall be without damage at time of Substantial Completion.
END OF SECTION