g. Overload Rating:
1) Normal Operation:
a) 150 percent for 1 minute.
b) 125 percent for 10 minutes.
c) 100 percent continuous.
2) Bypass Operation:
a) 100 percent continuous.
b) 800 percent for 500 milliseconds.
h. System AC-AC Efficiency: Greater than 93 percent at full load with 208 volt supply.
i. Output Power Factor Rating: 0.8 at full load.
j. Slew Rate: 0.25 to 1 hertz/second.
1.5 SUBMITTALS
A. General: See [Section 01 33 00 - SUBMITTAL PROCEDURES] [Section 01300 - SUBMITTALS].
B. Product Data: Submit product data showing material proposed. Submit sufficient information to
determine compliance with the Drawings and Specifications. Product data shall include, but shall
not be limited to, the following:
1. As bid system bill of materials.
2. Product catalog sheets or equipment brochures.
3. Product guide specifications.
C. Shop Drawings: Submit shop drawings for each product and accessory required. Include
information not fully detailed in manufacturer’s standard product data, including, but not limited to,
the following:
1. Installation information, including, but not limited to, weights and dimensions.
2. Information about terminal locations for power and control connections.
3. Drawings for requested optional accessories.
D. Wiring Diagrams: Submit wiring diagrams detailing power, signal, and control systems, clearly
differentiating between manufacturer-installed wiring and field-installed wiring, and between
components provided by the manufacturer and those provided by others.
1. Submit system single-line operation diagram.
E. Operation and Maintenance Data: Submit operation and maintenance data to include in operation
and maintenance manuals specified in [Division 01 - GENERAL REQUIREMENTS]
[Division 1 - GENERAL REQUIREMENTS], including, but not limited to, safe and correct operation
of UPS functions.
1. Submit an installation manual, which shall include, but shall not be limited to, instructions for
storage, handling, examination, preparation, installation, and start-up of UPS.
2. Submit an operation and maintenance manual, which shall include, but shall not be limited to,
operating instructions.
1.6 QUALITY ASSURANCE
A. Qualifications:
1. Manufacturer Qualifications: Manufacturer shall be a firm engaged in the manufacture of
solid state UPS of types and sizes required, and whose products have been in satisfactory use
in similar service for a minimum of 20 years.
a. The manufacturer shall be ISO 9001 certified and shall be designed to internationally
accepted standards.
2. Installer Qualifications: Installer shall be a firm that shall have a minimum of five years of
successful installation experience with projects utilizing solid state UPS similar in type and
scope to that required for this Project.