APC ACRC103 Dokumentacja Strona 26

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 44
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 25
InRow Half-Rack RC Installation20
Filling and Purging
When the equipment is properly piped, begin the filling process (top piping configuration shown).
Electrical Hazard: Ensure both electrical connections are disconnected before introducing
water into the equipment.
1. Open the 2-way supply valve and the 2-way bypass shutoff valve.
2. Using a 2.5-mm hex key, turn the flow control actuator to the fully open position.
na1767a
Flow control
actuator
Fully open
Full bypass
Fully open
Fully open
2-way supply
valve
2-way bypass
shutoff valve
Fully closed
Fully closed
Przeglądanie stron 25
1 2 ... 21 22 23 24 25 26 27 28 29 30 31 ... 43 44

Komentarze do niniejszej Instrukcji

Brak uwag