InRoom CW/DX – Operating Instructions42
Hazards with incorrectly fi lled systems
Overfi lling
Overfi lling the system inevitably results in a high condensing pressure and loss of cooling capacity. The high
pressure switch can be triggered as a result.
Underfi lling
A system which is insuffi ciently fi lled results in the following:
Output reduction due to evaporation temperatures which are too low, and triggering of the low pressure
switch. Excessive overheating temperature which can result in compressor damage.
Note:
Recommended superheating:
12 - 18°F (7 - 10 K)
Recommended subcooling:
> 3.6°F (2 K)