APC INROOM ACPSC3000 Instrukcje Operacyjne Strona 51

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 80
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 50
InRoom CW/DX – Operating Instructions
51
Caution:
The unit must be installed and connected in accordance
with all state and local government regulations prior to
initial commisioning.
• Make sure that the disconnect switch is off and the unit is de-ener-
gized.
Open the electrical compartment door of the unit using the key provided.
• Check whether all power switches and control-circuit fuses in the
electrical section of the unit are switched off.
• Retighten all screw connections in the electric cabinet.
• Verify the smooth function of the contactors.
• Switch on the cooling unit at the disconnect switch.
• Switch on the control-circuit fuses and the power switches of the
fan and the compressor in sequence.
The controller is now supplied with power, so you can use it for ad-
justments.
Make sure that the heat rejecting system is operating.
A - air-cooled condenser
G, GE - dry cooler
ACW - air-cooled condenser + chiller
GCW - dry cooler + chiller
Switching on
power switch
Electrical
compartment
Power switch off
Control-circuit
fuses
Power switches
Master switch
7. Commissioning
Electrical Hazard:
Do not turn the adjustment screw beyond the end of the calibrated scale range, as it may
result in overheating and short-circuit at the electrical component or in the destruction of
the power switch.
non-calibrated range
Przeglądanie stron 50
1 2 ... 46 47 48 49 50 51 52 53 54 55 56 ... 79 80

Komentarze do niniejszej Instrukcji

Brak uwag