990-1467C InfraStruXure System – Service Manual – Installation and Start-Up 39
Install Shielding Troughs, Shielding Partitions, and
Cable Ladders
Shielding Troughs and Shielding Partitions for overhead wiring along rows
If you ordered APC Shielding Troughs, Shielding Partitions, and Cable Ladders to route overhead wiring
for your system, assemble the Shielding Troughs and the Shielding Partitions along the rows of
enclosures and assemble the Cable Ladders between rows.
For detailed information and grounding instructions, see the instruction sheet included with the
Shielding Troughs and Shielding Partitions
(990-1393B).
Shielding Trough accessories. APC offers the following accessories for Shielding Troughs:
Shielding Trough Covers for both 600-mm wide (AR8174BLK) and 750-mm wide (AR8175BLK)
enclosures. Contact APC for more information.
Shielding Trough End Caps (AR8167BLK) to place on the side of a Shielding Trough at the end of
a row. Contact APC for more information.
Shielding Troughs. There are two types of Shielding Troughs:
The PDU Wide Shielding Trough is 610mm in length and is not adjustable. The trough sits on
top of the InfraStruXure PDU. The PDU Shielding Trough is two pieces. The power cables sit
in between the two pieces when installed on the roof of the PDU.
The NetShelter Shielding Trough is 610mm in length and is not adjustable. The Shielding
Troughs have an opening in each side through which you route data cables to the Shielding
Partitions.