Start-Up Procedure
990-1467C InfraStruXure System – Service Manual – Installation and Start-Up 55
The UPS interface displays the following fault screen:
b. Press any key.
The UPS interface displays the following fault screen:
c. Press the
ESC key.
The LOAD ON LED illuminates and the interface displays the following screen:
After you have verified that the UPS operates correctly in on-battery operation, shut-down the UPS:
1. Command the UPS to turn off power to the load:
a. Press the
E
SC
key at the top-level status
screen to open the top-level menu and have
access to eight submenus.
b. Select Control, and press the
E
NTER
key.
Top-Level Menu
c. Select Tur n Lo ad O ff from the Control
menu, and press the
E
NTER
key.
Control Menu
d. On the next screen: select Ye s , UPS Load
OFF, and press the
E
NTER
key.
Confirmation Screen
The LOAD ON LED turns off and the interface displays the following two screens:
Bypass not available
Press any key...
Input Freq/Volt out of range
End of Fault List
keys to view list again
Press Esc to exit or other
UPS load is on
Press any key...
Control
Status
Setup
Accessories
Logging
Display
Diags
Help
UPS Into Bypass
Do Self Test
Simulate Power Fail
Graceful Reboot
Graceful Turn Off
Start Runtime Cal
Turn Load Off
Confirm
Yes, UPS Load OFF
No, Abort
UPS has been
commanded to turn
load power off...
UPS load is off
Press any key...