Installation ProceduresRoute and Attach Overhead Wiring
44 InfraStruXure System – Service Manual – Installation and Start-Up 990-1467C
For dual-feed devices within a redundant system: attach a power cable from each PDU into two
different Rack PDUs in the NetShelter VX Enclosure.
For single-feed devices within a redundant system with an Automatic Transfer Switch: connect a
power cable to the Automatic Transfer Switch (A and B feeds) and connect the Automatic
Transfer Switch power cord to a Rack PDU in the NetShelter VX Enclosure.
For dual-feed devices in a redundant system with an Automatic Transfer Switch: connect a
power cable from each PDU to the Automatic Transfer Switch’s A and B feeds, and another
power cable from one PDU to a Rack PDU, and the Automatic Transfer Switch’s power cord to a
second Rack PDU in the NetShelter VX Enclosure.
Note: Lay the cables neatly in the Shielding Trough to minimize cable build-up.