Start-Up Procedure
990-1467C InfraStruXure System – Service Manual – Installation and Start-Up 61
2. Close (turn ON) the Q3 circuit breaker on the InfraStruXure PDU.
Note: The H2 LED above the Q2 circuit breaker illuminates, indicating that it is safe to operate
the Q2 circuit breaker.
3. Open (turn OFF) the Q2 cirucit breaker on the InfraStruXure PDU.
The UPS will display a Forced Bypass message on the display interface and the Fault LED will be red.