Appendix A : System OperationHow to Return from Maintenance Bypass Operation
72 InfraStruXure System – Service Manual – Installation and Start-Up 990-1467C
Note: The H2 LED above the Q2 circuit breaker illuminates, indicating that it is safe to operate
the Q2 circuit breaker.
Note: The H3 LED above the Q3 circuit breaker illuminates, indicating that it is safe to operate
the Q3 circuit breaker
c. Select UPS Into Bypass on the Control menu, and
press the
E
NTER
key.
Control Menu
d. Confirm the selection on the next screen: select Yes ,
UPS into Bypass, and press the
E
NTER
key.
Confirmation Screen
7. Close (turn ON) the Q2 circuit breaker on the PDU.
8. Open (turn OFF) the Q3 circuit breaker on the PDU.
The UPS automatically comes out of Static Bypass
operation.
UPS Into Bypass
Do Self Test
Simulate Power Fail
Graceful Reboot
Graceful Turn Off
Start Runtime Cal
Turn Load On
Confirm
Yes, UPS into Bypass
No, Abort