APC INROOM ACPSC3000 Instrukcje Operacyjne Strona 13

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 106
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 12
13InRoom Controller - Operating Instructions
Pin Designation DX1 DX2 CW
1 +Ub/Ib
Universal sensor 4
Outside temperature
Universal sensor 4
Outside temperature
Universal sensor 4
Outside temperature
2 Ain 6
3 GND
4 GND
5 +Ub/Ib
Universal sensor 5
Condensation pressure
Universal sensor 5
Condensation pressure 1
Universal sensor 5
Water temp. 2 (CW2)
6 Ain 7
7 GND
8 GND
9 +Ub/Ib
Universal sensor 6
Evaporation pressure
Universal sensor 6
Condensation pressure 2
Universal sensor 6
- free -
10 Ain 8
11 GND
12 GND
13 +Ub/Ib
Universal sensor 7
Water temp. (G)
Universal sensor 7
Water temp. (G) or evapo
-
ration pressure 1
Universal sensor 7
- free -
14 Ain 9
15 GND
16 GND
17 Aout 5
Suction valve / compres
-
sor1 or actual humidity
Suction valve / compres-
sor1 or actual humidity
Actual humidity
18 GND
19 Aout 6
Actual temperature
Suction valve /
compressor 2/ act. temp.
Actual temperature
20 GND
21 Aout 7
HWR valve HWR valve HWR-valve
22 GND
23 Aout 8
EEV (with 0-10V) or pro-
portional dehumidification
EEV (with 0-10V) or pro-
portional dehumidification
Proportional
dehumidification
24 GND
X10
SUB-D 15 Bus 3 I
2
C (plug) Bus 3 I
2
C (plug) Bus 3 I
2
C (plug)
2.3.2 Assignment - EAIO
The assignment depends on the unit version (DX1, DX2, CW). For more information, see „2.1.2 Assignment - I/O Controller“
on page 7.