InRoom Controller - Operating Instructions58
➊
➋
➌
➍
➎
K2
Service
The corresponding commands:
Times are entered in hours.
The numbered callouts refer to the corres
-
ponding passages in the descriptive text.
Display Cooling
Compressor
In the first line you add the compressor
to the configuration by entering "1". With
"0" you disable the compressor although
all settings concerning the compressor
are kept.
➊
You can determine a digital output for the
compressor on/off signal. ➋
The digital input for the compressor alarm
can be assigned in the third line.
➌
The digital input for the low pressure alarm
can be assigned in the fourth line.
➍
The compressor runtime can be adjusted
in the last line. ➎
comp 1 conf 1
comp 1 dout 3
comp 1 alarm 5
comp 1 alarmlp 7
comp 1 runtime 10