83InRoom Controller - Operating Instructions
Range Compressor 1 Compressor 2
Summer start
0 - 9.9 0.4 K 0.6 K
Summer hysteresi
s 0 - 9.0 0.7 K 0.7 K
Winter start
0 - 9.9 0.7 K 0.9 K
Winter hysteresi
s 0 - 9.0 0.7 K 0.7 K
Component configure
d 0 - 1 0 0
Output D 0 - 31 2 7
Alarm input
D 0 - 43 2 8
Alarm priority
0 - 31 0 0
Common alarm
0 - 1 1 1
Alarm delay
0 - 100 5 s 5 s
Alarm input
LP 0 - 43 3 9
Alarm priority
LP 0 - 31 2 2
Common alarm
LP 0 - 1 1 1
Alarm delay
LP 0 - 100 5 s 5 s
LP management time 0 - 100 0 h 0 h
LP management press. 0 - 10 5 bar 5 bar
LP management restart
0 - 10 0 0
HP management time 0 - 100 0 h 0 h
HP management press.
0 - 35 21 bar 21 bar
HP management restart
0 - 10 0 0
HP management mode 0 - 1 0 0
Pause
10 - 1000 180 s 180 s
Runtime
0 - 4294967295 0 h 0 h
Suction valve 1 Suction valve 2
Start
0 K (0 - 9.9) 0.4 K (0 - 9.9)
Gradient
0.5 K (0.5 - 9.9) 0.5 K (0,5 - 9.9)
Component configure
d 0 0
Output A 5 (0 - 20) 6 (0 - 20)
GE/CW-Valve
Start
0.1 K (0 - 9.9)
Gradient
0.6 K (0,5 - 9.9)
Component configure
d 0
Output A 1 2 (0 - 20)
Output A 2 4 (0 - 20)
Input D 0 (0 - 43)
GE-off 23°C (0 - 50)
Setpoint 95% (50 - 100)
G-Valve
Pressure setpoint 18 bar (5 - 25)
Component configure
d 0
Control cycle 5 s (1 - 10)
Max. alternation
2% (1 - 10)
Control factor
4 (1 - 10)
Output A 4 (0 - 20)
Pre-open time 30 s (0 - 255)
Pre-opening 100 (0 - 100)
Components
Compressor
Valves