InRoom Controller - Operating Instructions16
3. Operator interface
3.1 I/O Controller
A keyboard is used to operate the I/O controller by using
specified commands that follow an easily understood
syntax.
To establish the connection from a PC to the IOC a 9-line
cable with SUB-D 9 connectors at both ends (crossed
type), which can be obtained as an option, is needed.
A terminal program is also needed. You can download
the terminal program "Service" from the APC website
www.apc.com. Connect the cable at a serial port of
your PC and at the service port X15 on the IOC. Start
the terminal program.
You can now communicate with the connected I/O con
-
troller (ioc), and in return the IOC sends the following
prompt to your PC:
"ioc ##:>", where ## represents the bus id.
The commands can be classified into three major categories:
1. Bus specific control commands
2. Commands related to cooling unit components
3. Commands concerning the whole cooling unit
1. Bus command 2. Component command 3. Cooling unit command
Each command displays a detailed help for further
parameters (if there are any) when it is followed by "h"
such as "comp h".
A command of the second (component command) or
third category (Cooling unit command) which is typed
in without any parameters displays all the information
about its subject (except "loaddefault ###" which is an
execution command).
The bus commands except for iobusare control com
-
mands that are executed after pressing the enter key.
The bus commands on a dark-gray (green) background
need the bus I.D.s of their respective units in order to
execute.
The commands on a light-gray (yellow) background need
no further parameters. The commands which are followed
by a number need this number because there are several
components of the same type.
sensor 1
comp 1
suctionv 1
gecwv
gvalve
drycool 1
pump 1
eheat 1
gasheat
pwwheat
humi 1
dehumi
fan 1
louver 1
equip
is 1
state
ups
wprg
event
log 1
option
exalarmin 1
zone 1
loaddefault dx1
invite ##
del ##
iobus
checkbus
spreadbusconf