39InRoom Controller - Operating Instructions
➊
➋
200%
100%
75%
50%
➋➊
200%
175%
100%
75%
50%
➋➊
200%
150%
100%
75%
50%
➋➊
A3
Control
The corresponding commands:
Times are entered in seconds.
The numbered callouts refer to the corres-
ponding passages in the descriptive text.
Display Valves
Suction valve
The start temperature for the suction valve
is entered as a positive difference to the
room temperature setpoint. ➊
You can adjust a gradient, which deter-
mines the temperature range in which
the valve opening increases from 0 to
100%.➋
If the cooling unit is equipped with two
refrigerant circuits, only the first refrigerant
circuit can be equipped with a suction
valve.
Depending on how you choose the start
points for the compressors you can
exploit the proportional control range of
the suction valve to a maximum. (See
examples.)
The suction valve has a control range of
50% - 100% of the compressor cooling
capacity.
Comp. 1
Comp. 2
Comp. 1 Comp. 2
Setpoint
Cool.
cap.
Comp. 1
Comp. 2
Comp. 1 Comp. 2
Cool.
cap.
Setpoint
Comp. 1
Comp. 2
Comp. 1 Comp. 2
Cool.
cap.
Setpoint
Suction
valve
Suction
valve
Suction
valve
Graphic A Graphic B Graphic C
The graphics A-C show, for a
DX2-unit, how you obtain a double
proportional control range by ap
-
proaching the stop point of the 2nd
compressor to the start point of the
suction valve.
suctionv 1 start 0.2
suctionv 1 grad 0.9