71InRoom Controller - Operating Instructions
Gen. setting
Control/Parameter (Part 3)
Cooling priority
The cooling priority determines the overriding cooling
circuit for units with two different cooling systems. The
parameters 0, 1, and 2 can be adjusted.
0 - no priority, this is the adjustment for GE-systems,
where a mixed operation of both systems is possib
-
le.
1 - CW- means that chilled water cooling has priority at
ACW/GCW-units.
2 - DX- means that compressor cooling has priority at
ACW/GCW-units.
Malfunction change-over
CW –> DX
Malfunction change-over
DX –> CW
The diagram below displays the conditions for a mal
-
function change-over at Dual-Fluid-units (units with two
different cooling systems).
WT > TGEoff
cooling priority = 1 CW-off = 1
CW-off = 0
cooling priority = 2
LP-alarm 1
compressor-
failure 1*
*HP-alarm or com-
pressor failure
LP-alarm 2
compressor-
failure 2*
- logic operation AND
- logic operation OR
WT - water temperature 1
TGEoff - upper water temperature limit for GE-operation
CW-off - digital input (pre-set DIN16) to enable DX-opera-
tion or to disable CW-operation(see page 80)
For a better understanding:
The OR-operations are horizontally located.
The AND-operations are vertically located.