InRoom Controller - Operating Instructions44
➊
➋
➌
➍
➎
➏
➊
➋
➌
➊
➋
T/°C
➊
➋
➊
➌
T/°C
F3 F5 F6
T/°C
➊
➌
➌➌
Control
The corresponding commands:
Times are entered in seconds.
The numbered callouts refer to the corres-
ponding passages in the descriptive text.
Display Heating
E-heating/Hotgas reheat/Hot
water reheat
Depending on which heating type you
have configured, different parameters
are decisive.
The start temperature for every heating
type is entered as a negative difference to
the room temperature setpoint. ➊
The hysteresis for the heating stop is only
valid for heatings with on/off-control.
➋
For proportional e-heatings/hot water
reheats you can adjust a gradient, which
determines the temperature range in
which the heating capacity increases from
0 to 100%.➌
You can determine, whether the e-heating
alarm releases a common alarm (0 = no,
1 = yes).
➍
The e-heating alarm delay can be adjus-
ted in seconds.
➎
Setting the priority for the heating alarm
➏ means assigning the corresponding
alarm to an alarm relay with the adjusted
number.
Only the first heating can be proportional.
If this is the case and if there are several
heatings (up to 4), only the start value
and the gradient of the first heating are
decisive for the control. Each time the pro
-
portional heating reaches 100% heating
capacity another reheat is added and the
first heating is reset to 0%. This way up to
four individual heatings act as one propor-
tional heating. (See illustration 1).
setpoint
setpoint
On/Off-control
Heating
ON
OFF
Proportional
Heating
100%
0%
3rd reheat
2nd reheat
1st reheat
total
Added heat capacities
on
off
on
off
100%
0%
300%
200%
100%
0%
setpoint
Illustration 1
eheat 1 start 0.2
eheat 1 hys 0.7
eheat 1 grad 0.9
eheat 1 commonalarm 1
eheat 1 alarmdelay 3
eheat 1 alarmprio 3
pwwheat 1 start 1.3
pwwheat 1 hys 0.6
pwwheat 1 grad 0.5
gasheat 1 start 1.3
gasheat 1 hys 0,6