61InRoom Controller - Operating Instructions
K7
➊
➋
➌
➍
➎
➏
➐
➑
Service
The corresponding commands:
Times are entered in hours.
The numbered callouts refer to the corres
-
ponding passages in the descriptive text.
Display Cooling
Pumps
By setting the parameter "ACTIVE" on 1 you
add a pump to the configuration. With "0" you
disable the pump.
➊
In the next line you determine which type the
pump shall belong to (1 = G-pump, which
pumps the medium through the condenser
in a GE2-unit, 2 = GE-pump, which pumps
the medium through the free cooling coil in
a GE2-unit, 3 = Glycol-pump - all pumps for
G-, GE1 units which are located outside the
cooling unit).
➋
With the parameter "D-OUT" you determi-
ne a digital output for a glycol pump on/off
signal. ➌
With the parameter "A-OUT" you adjust the
analogous output of the proportional signal
for a G/GE-pump.
➍
The digital input for the pump alarm can be
assigned by the "D-IN" parameter. ➎
The pump runtime can be set in the next
line. ➏
For glycol pumps you can enable a sequen-
cing based on time and failure. With "partner
unit" ➐ and "partner pump" ➑ you select the
number of the 2nd pump and the ID of the
unit from which this pump is controlled.
pump 1 conf 1
pump 1 type 2
pump 1 dout 3
pump 1 aout 4
pump 1 alarm 3
pump 1 runtime 60
pump 1 partunit 17
pump 1 partpump 1