Control
The corresponding commands:
Times are entered in seconds.
The numbered callouts refer to the corres-
ponding passages in the descriptive text.
Display Humidification
Humidifier
Depending on which humidifier type you
have, different parameters are decisive.
The start humidity for every humidifier is
entered as a negative difference to the room
humidity setpoint.
➊
The hysteresis for the humidifier stop is only
valid for humidifiers with on/off-control.➋
For proportional humidifiers you can adjust
a gradient, which determines the humidity
range in which the humidifying capacity
increases from 0 to 100%.➌
You can determine, whether the humidifier
alarm releases a common alarm (0 = no,
1 = yes).
➍
The humidifier alarm delay can be adjusted
in seconds.
➎
Setting the priority for the humidifier alarm ➏
means assigning the corresponding alarm to
an alarm relay with the adjusted number.
In the following window you can adjust the
three parameters: common alarm
➍a ➍b,
alarm delay ➎a ➎b and alarm priority ➏a
➏b for the conductivity alarm at 5µS and
at 20µS.
These alarma are available with the applica
-
tion of a conductivity measuring instrument,
which is required to control the water con-
ductivity for Ultrasonic humidifiers.
On/Off-control
(type 1)
Humidifier
ON
OFF
Proportional (type 2)
Humidifier
100%
0%
setpoint
setpoint
%r.h.
%r.h.
humi 1 start 7.3
humi 1 hys 9.0
humi 1 grad 10.0
humi 1 commonalarm 1
humi 1 alarmdelay 6
humi 1 alarmprio 5
humi 1 commonalarm5 1
humi 1 alarmdelay5 6
humi 1 alarmprio5 5
humi 1 commonalarm20 1
humi 1 alarmdelay20 6
humi 1 alarmprio20 5