InRoom Controller - Operating Instructions30
Info
Display
If your cooling unit is equipped with a
heater, the operating state is displayed in
this window. For proportional heaters the
actual capacity is shown from 0-100%.
For the hot water reheat the actual ca
-
pacity is displayed in the shape of the
opening degree of the HWR valve.
If your cooling unit is equipped with a hu
-
midifier, the operating state and the degree
of steam production of the humidifier is
displayed in this window.
In addition the display indicates whether
the dehumidication is switched on or
off.
The operating state of the fans with the
actual speed from 0-100% is indicated in
this window. If your cooling unit is equipped
with louvers, -1- indicates that the louver
is open.
In the following windows you can see the
operating state of each component:
-0- means component is off.
-1- means component is on.
xxx means component does not exist.
This window displays the opening degree
of the valves in a percentage from 0 to
100.
On/off state of the dry coolers
On/off state of the pumps + actual capacity
in %, if the pumps are speed controlled.
This table shows digital and analog in-
puts/outputs and displays 0 or 1 for each
digital input/output, which could be helpful
for diagnosis purposes.
In the first line the inputs from 1 to 4 are
displayed, in the second line the inputs
from 5 to 8 etc.
Module state
InRoom Controller gives a detailed rep-
resentation of the operating states of the
components.
Display
Signification
D-IN
1
voltage present -> no
alarm
D-OUT
1
relay activated -> compo
-
nent in service
A-IN
0-4095
0-20mA, 4-20mA, 0-10V
corresp. to sensor type
A-OUT 0-4095 0-10V
Przeglądanie stron 29