51InRoom Controller - Operating Instructions
➊
➋
➌
➍
➎
➏
❼
❽
T/°C
➑
➏
➐
DXmax/
CWmax
D6
Control
The corresponding commands:
Times are entered in seconds.
The numbered callouts refer to the corres-
ponding passages in the descriptive text.
Display Air
Fan (Part 4)
The "DEHUM.SPEED" ➊ is entered as a
negative difference in % to the maximum
speed. This is the fan speed for the first option
of dehumidification.
The "UPS SPEED"
➋ is also entered as a
negative difference in % to the maximum
speed. When the controller receives a UPS
signal the controller will apply this reduced
speed for an emergency operation.
The parameters:
- control cycle ➌
- max. control correction ➍
- control factor ➎
are only necessary for the GEp-control,
which is explained in a separate manual.
If the cooling unit has low airflow during nomi
-
nal operation, the fan speed can be raised
when the temperature setpoint is exceeded.
The fan speed increase depends on the
temperature difference to the setpoint.
For this way of cooling the room by increas-
ing the fan speed you adjust a positive
temperature difference
➏ to the setpoint,
which represents the start point of the speed
increase.
Then you adjust a maximum speed
➑ for the
overload operation and another temperature
difference
➐ to the setpoint, which marks the
end of the proportional fan speed increase.
Having attained the second temperature
difference, the fan is operated with the
maximum speed for the overload operation.
This speed is kept even if the temperature
continues to rise.
Setpoint
Fan speed
fan 1 dehum 25
fan 1 ups 35
fan 1 concyc 8
fan 1 maxc 2
fan 1 fact 2
fan 1 emerstart 0.7
fan 1 emerend 2.0
fan 1 emernmax 95