InRoom Controller - Operating Instructions72
Service
Display Day & Night
The week timer is based upon two diffe-
rent temperature setpoints which you have
already adjusted in the control/tempera
-
ture menu. Setpoint 1 is represented by a
thick line, setpoint 2 by a dotted line.
For each hour of each day of the week you
choose among three settings:
Display:
1. Cooling unit off 0
2. Cooling unit on with setpoint 1 1
3. Cooling unit on with setpoint 2 2
Sets the timer stop mode for
monday from 12:00 to 12:59
Day: Hour: Status:
mo = monday 0 = from 0:00 to 0:59 0 = Cooling unit off
tu = tuesday 1 = from 1:00 to 1:59 1 = Cooling unit on with setpoint 1
we = wednesday 2 = etc. 2 = Cooling unit on with setpoint 2
th = thursday
fr = friday
sa = saturday
su = sunday
The corresponding commands:
Display in the main menu when
the timer program is executed:
wprg mo 12 0