InRoom Controller - Operating Instructions76
Stand
-by
Stand
-by
Zone 01
Cycle 1
Unit 01 Unit 03 Unit 07
Unit 08 Unit 11 Unit 14
Example for a Sequencing configuration:
The zone shown on the right is to be configured.
- All alarms shall remain valid.
- The number of defective units shall be 3.
- The emergency temperature shall be 17°C.
- The sequencing cycle shall be 5 hours.
1. Determinating the standby units in the general overview
Select the units one by one and set the operating status by means of the ON/OFF
switch at the InRoom Controller. A locally stopped unit is counted as a standby
unit at the start of the sequencing.
IOC 07 operating status: Stop IOC 11 operating status: Stop
2. Unit assignment
Now the units 01, 03, 07, 08, 11 and 14 are assigned to zone 01. This must be done
separately for each unit in the menu "Service/Gen. settings/Sequencing".
3. Number of defective units
Settings can also be made in this menu concerning the zone in total.
The number of defective units is part of these adjustments.
4. Emergency temperature
Set the emergency temperature to 17°C.
5. Sequencing cycle
Entering the sequencing cycle starts the sequencing.
6. Switching on the standby units
The standby units 07 and 11 must now be selected in the overview and be switched
on by setting "1" in menu item "standby".
Commands
At the configuration by the terminal
program the sequence is different. First
assign the units to the zone, then set
the standby units.
Switching on the standby units belated
-
ly is not necessary here.
zone 1 + 1
zone 1 + 3
zone 1 + 7
zone 1 + 8
zone 1 + 11
zone 1 + 14
zone 1 unit 7 0
zone 1 unit 11 0
zone 1 emernum 3
zone 1 emertemp 17
zone 1 seqtime 5
Przeglądanie stron 75