APC INROOM ACPSC3000 Instrukcje Operacyjne Strona 64

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 106
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 63
InRoom Controller - Operating Instructions64
P1
P3
Service
The corresponding commands:
Times are entered in hours.
The numbered callouts refer to the corres
-
ponding passages in the descriptive text.
Display Air
Fan
Setting the parameter ACTIVE to 1 adds a
fan to the configuration. Setting this parame-
ter to 0 disables the fan.
In the next line you determine the fan type
(1: fan with on/off control, 2: EC-fan with
proportional speed control).
With the parameter "D-OUT" you determine
a digital output for an on/off fan.
With the parameter "A-OUT" you adjust the
analogous output of the proportional signal
for a speed controlled fan.
The digital input for the airflow alarm can be
assigned by the "D-IN" parameter.
The digital input for the filter alarm can be as-
signed by the "D-IN FILTER" parameter.
The fan runtime can be set in the last line.
Louver
Setting the parameter ACTIVE to 1 adds
a louver to the configuration. Setting this
parameter to 0 disables the louver.
With the parameter "D-OUT" you determine
a digital output for the louver.
fan 1 conf 1
fan 1 type 1
fan 1 dout 11
fan 1 aout 11
fan 1 alarm 2
fan 1 filteralarm 6
fan 1 runtime 120
louver 1 conf 1
louver 1 dout 11
Przeglądanie stron 63
1 2 ... 59 60 61 62 63 64 65 66 67 68 69 ... 105 106

Komentarze do niniejszej Instrukcji

Brak uwag