25InRoom Controller - Operating Instructions
6. Operation
6.1 Info level
6.1.1 Info commands
Generally each component- or cooling unit-command that is entered without parameters only displays information
without changing adjustments. However, the following commands give a general overview about the unit state and
configuration.
equip - Shows the components and their numbers and the extension cards (digital/analogous).
state - Shows the unit and functional (cooling, heating etc.) runtimes and the unit/component state.
is 1 - - Setpoints, actual zone/unit values, limit values.
is 2 - - Alarm delay, priority, common alarm assignment for each limit value alarm.
is 3 - - Control type, sensor limitation values, cooling priority, winter operation, UPS mode, outside tempera-
ture for
condensation pressure reduction, gradient for pressure reduction, winter start delay, bus/global
address,
temperature difference for overload activation, last service, service interval.
- Assignment of in/outputs: common alarm, winter operation, remote on/off, UPS operation, actual
temperature/humidity, CW cooling off.
wprg - Shows the programmed timer function for the week.
events - Shows all registered events (maximum 200, alarms & unit on/off).
ups - Shows the UPS (uninterrupted power supply) configuration.