InRoom Controller - Operating Instructions92
Component Alarm input on board Alarm
Compressor 1 DIN 2 IOC COMP 1 FAILURE/HP
DIN 3 IOC LOW PRESSURE 1
Compressor 2 DIN 8 IOC COMP 2 FAILURE/HP
DIN 9 IOC LOW PRESSURE 2
Fan
DIN 1 IOC AIRFLOW FAILURE 1
DIN 5 IOC FILTER 1 ALARM
E-heating DIN 4 IOC E-HEAT # FAILURE
Steam-Humidifier
DIN 6 IOC HUMIDIFIER 1 FAIL
GE-pump DIN 13 EDIO 1 GE-PUMP 1 FAILURE
G-pump DIN 14 EDIO 1 G-PUMP FAILURE
Drycooler
DIN 15 EDIO 1 DRYCOOLER 1 FAIL
7.3 Component-related alarms
The table shows the main components with their standard alarm input and the possible alarms.
7.4 Alarm Reset
The alarms are reset by pressing the RESET-key. Pressing it once mutes the alarm tone. Pressing it again resets
all alarms. However, if the alarm cause has not been eliminated, the alarm will appear again.
Alarms can either be reset in the standard window for each single unit or in the bus configuration overview by
marking all bus participants for all units.
Command
The alarms for one unit are reset with the command "alarmreset".
DX/DX2-unit:
Component Alarm input on board Alarm
Fan DIN 1 IOC AIRFLOW FAILURE 1
DIN 5 IOC FILTER 1 ALARM
E-heating DIN 4 IOC E-HEAT 1 FAILURE
Steam-Humidifier
DIN 6 IOC HUMIDIFIER 1 FAIL
Pump 1 DIN 2 IOC PUMP 1 FAILURE
Pump 2 DIN 14 EDIO 1 PUMP 2 FAILURE
ext. Chiller
DIN 3 IOC CHILLER FAILURE
CW/CW2-unit: